PRELIMINARY DESIGN OF A HEAVY TIMBER STRUCTURE
Estimate the depth of solid wood beams at 1 /15 of their span and the depth of glue-laminated beams at 1/ 20 of their span. Add a nominal 6 inches (150 mm) to these depths for girders. The width of a solid wood beam or girder is usually 1 /4 to 1 /2 of its depth. The width of a glue-laminated beam typically ranges from 1 /7 to 1 /4 of its depth.
Estimate the depth of timber triangular roof trusses at 1 /5 to 1 /2 of their span and the depth of bowstring trusses at 1 /2 to 2/ 3 of their span.
To estimate the size of a wood column, add up the total roof and ß oor area supported by the column. A nominal 6- inch (actual size 140 mm) column can support up to about 400 square feet (37 m2) of area, an 8-inch (actual size 184 mm) column 1000 square feet (93 m2), a 10-inch (actual size 235 mm) column 1500 square feet (140 m2), a 12-inch (actual size 286 mm) column 2500 square feet (230 m2), and a 14-inch (actual size 337 mm) column 3500 square feet (325 m2). Wood columns are usually square or nearly square in proportion.
For actual sizes of solid timbers in conventional units, see Figures 3.22 and 3.23. Standard sizes of glue-laminated timbers are given in Chapter 3. For a building that must qualify as Type IV Heavy Timber construction under the IBC, minimum timber sizes are given in Figure 4.7.
![]() |
| Figure 3.23 A complete chart of nominal and actual dimension for both framing lumber and finish lumber |
These approximations are valid only for purposes of preliminary building layout, and must not be used to select final member sizes. They apply to the normal range of building occupancies such as residential, office, commercial, and institutional buildings. For manufacturing and storage buildings, use somewhat larger members.